TROX Automatic Poppet Valve ATVC-100

TROX HESCO Schweiz AG

Description

Automatic poppet valves type ATVC-100 are suitable for installation in multi-storey residential and commercial buildings, hotels, schools, etc. with central exhaust air systems. ATVC-100 can be installed in new buildings as well as in old building renovations.

More Over

Design:

The automatic poppet valve is an exhaust air device that works with auxiliary electrical energy. Normally, the automatic poppet valve is closed or only slightly open for a basic volume flow. The increased operating volume flow is only extracted when the corresponding switching contact is closed.

Function

After the circuit is closed, the electrothermal actuator heats up and causes the valve disc to open within 2 – 4 minutes (delay in case of short-term stay). The air is extracted through the resulting opening between the valve housing and the valve disc. The valve lift (6 mm) is always the same size, i.e. the valve disc always moves from the selected minimum setting to the maximum valve opening. In the minimum setting, the poppet valve can be closed or open. Because the valve lift is always the same size, the operating volume flow cannot be freely selected, but depends on the minimum setting. As long as the circuit remains closed, the poppet valve is open on the max. valve lift. After the circuit is interrupted, the automatic poppet valve remains open for re-ventilation for approx. 5-8 minutes before slowly and silently returning to the minimum setting.

Advantages

  • Heating energy can be saved as a result of targeted ventilation (basic volume flow/operating volume flow).
  • As a result of the built-in start-up delay, there is no increased volume flow when staying in the room for a short time.
  • Silent opening and closing of the poppet valve.
  • Poppet valve and electrothermal actuator made of proven components.
  • Easy installation.
  • Taking into account a simultaneity factor, the roof fan and the riser channel can be chosen smaller.
  • The poppet valve can be closed tightly.
  • Connection to the normal 230V 50Hz light network without additional delay relays (after-ventilation) or transformers.

Technical Information

Rated Voltage: 230V / 50Hz

Power Consumption Operating: 8W Max.

Ambient temperature: 30° C

Device for connection opening: Ø100 mm