More Over
Application
Technical Information
Nominal sizes W × H: 100 × 100 – 1250 × 2560 mm
Housing length: 200 mm
Volume flow range at 10 m/s: from 360 m³/h – 115110 m³/h or from 100 l/s – 31975 l/s
Differential pressure range: pressure level 3, -1500 – 500 Pa
Operating temperature: 30 °C – 50 °C without falling below the dew point
Inflow velocity with uniform inflow and outflow:
dimension range, see motor allocation matrix (technical clarification with TROX required for some sizes)
Leakage airflow with closed flap blade: EN 1751, at least class 2, from nominal diameter 840 × 480 class 3
Housing leakage airflow: EN 1751, class B, from nominal diameter 840 × 480 Class C
EC conformity: EU Construction Products Regulation No. 305/2011
Declaration of performance: DoP/EK-JS/001
☛ brochure
Downloads